48 Amp EV Charger Wire Size & Breaker for 50 Feet
Quick Answer: Use 6 AWG Copper (THHN / 6/2 NM-B) with a 60 Amp 2-Pole Breaker. A 48 Amp Level 2 EV charger is classified as a continuous load under NEC rules, requiring a 60A circuit breaker and minimum 6 AWG copper wire for a 50-foot run.
⚡ Interactive NEC Wire Size & Voltage Drop Calculator
US / Canada AWG StandardMinimum Wire Size
6 AWG
Copper (75°C NEC)
Breaker / Fuse Size
60 Amp
Includes 125% NEC factor
Voltage Drop
1.29%
PASS (Under 3% NEC limit)
Total Power
11.52 kW
Max Circuit Load
🛒 Complete Installation Materials Checklist
1. Recommended Wire
6 AWG THHN Copper Wire (50-100 ft Roll)
2. Breaker / Disconnect
60 Amp 2-Pole Circuit Breaker
3. Compatible Equipment
48 Amp Level 2 Hardwired EV Charger
📋 NEC Code & Installation Notes
- NEC 625.41 requires EV charging circuits to be sized at 125% of the continuous load (48A x 1.25 = 60A).
- Standard 6/2 NM-B Romex is rated for 55A at 60°C, so 6 AWG THHN/THWN-2 copper inside 3/4-inch conduit (rated 65A at 75°C) is required for full 48A charging.
- Hardwiring is mandatory for 48A chargers since NEMA 14-50 outlets max out at 40A continuous.
Frequently Asked Questions
What wire gauge do I need for 48 amp ev charger wire size & breaker for 50 feet?
For a 48A load at 240V over 50 feet, the recommended conductor is 6 AWG Copper (THHN / 6/2 NM-B) paired with a 60 Amp 2-Pole Breaker to meet NEC ampacity and keep voltage drop below 3%.
Can I use aluminum wire instead of copper for 48 Amps?
Yes, for feeder runs (such as subpanels or RV pedestals), aluminum THHN/XHHW or SER cable can be used if upsized by 1 to 2 AWG sizes (check the Aluminum option in our calculator above) and terminated with anti-oxidant compound on AL-rated lugs.
Why does distance affect wire size for Tesla Wall Connector / 48A Level 2 EV Charger?
Longer wire runs increase electrical resistance, causing voltage drop. Under NEC guidelines, keeping voltage drop under 3% prevents overheating, nuisance breaker trips, and reduced charging or motor efficiency.